Delaware Administrative Code
Title 1 - Authorities, Boards and Commissions
700 - Delaware State Fire Prevention Commission
702 - Fire Protection in Building Construction
Chapter 3 - Special Fire Safety Provisions For Physically Handicapped People
Section 702-3-1.0 - Areas of Refuge
Current through Register Vol. 28, No. 3, September 1, 2024
1.1 Definition. An area of refuge for a floor area is that space which is sufficiently protected from the heat and toxic gases produced by a developing fire in the floor area and which provides a direct access to an exit. An area of refuge is intended to facilitate a safe delay in egress from the story containing the floor area, thus constituting a safe space for the handicapped or otherwise disabled persons to await assistance for their safe evacuation.
1.2 Every mid-rise building and high-rise building shall incorporate areas of refuge which shall be established and maintained in accordance with this Chapter.
1.3 Every floor area of a mid-rise building and high-rise building where barrier free access is provided above the first story shall have not less than one area of refuge.
1.4 An area of refuge shall consist of one of the following:
1.5 Areas of refuge shall be designated as such on all building plans and identified as such within the building. Identification within the building shall incorporate the "International Symbol of Accessibility" and be tactile in texture in accordance with ANSI Standard A117.1-1986. Except for doors, glazed openings shall not be permitted in walls separating areas of refuge from the remainder of the floor area.