Connecticut Administrative Code
Title 19 - Public Health and Safety
411 - Vertical Wheelchair Iifts
Section 19-411-C12 - Electrical wiring in the machinery space and hoistways

Current through September 9, 2024

(a) Method of installation of wiring in hoistways. Stationary electrical conductors located in hoistways shall be encased in rigid metal conduits or electrical metallic tubing or metal conduits or metal wireways.

Exception: Flexible conduit or armored cables may be used between hoistway risers and limit switches, hoistway door interlocks or contacts and signal or stop buttons and similar devices. All conduits, armored cable, electrical metallic tubing, metal wireways and flexible conduits carrying electrical conductors located within hoistways shall be securely fastened to the hoistway construction or to the guide rails or to the guide rail supports.

(b) Wiring methods in hoistways and machinery spaces. The installation of all electrical wiring in hoistways and machinery spaces except as may be provided elsewhere in these rules shall conform to the requirements of the National Electrical Code, National Fire Protection Association 7-1978.

The flexible traveling cable, connecting the platform to the stationary hoistway wiring, shall be provided in a flame retardant and moisture resistant outer cover.

(c) Enclosure of live parts on platform and hoistway. All live parts of electrical apparatus, located in or on a platform or in their hoistways, shall be suitably enclosed to protect against accidental contact.

Disclaimer: These regulations may not be the most recent version. Connecticut may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.