Current through September 9, 2024
(a)
Definitions. As used in this
section:
(1) "Air gap" means the unobstructed
vertical distance through the free atmosphere between the lowest opening from
any pipe or outlet supplying water to a tank plumbing fixture, or other device,
and the flood level rim of the receptacle. The vertical physical separation
shall be at least two times the inside diameter of the water inlet pipe above
the flood rim level but shall not be less than one inch;
(2) "Air vent type backflow preventer" means
a device containing two independently operating check valves separated by a
chamber which can automatically vent to the atmosphere if backflow
occurs;
(3) "Atmospheric vacuum
breaker" means a mechanical device which automatically air vents a pipeline to
prevent backsiphonage;
(4) "Double
check valve assembly" (DCVA) means a device which contains two independently
acting check valves located between two tightly closing shutoff valves and
fitted with properly located test cocks;
(5) "Fire sprinkler system" for fire
protection purposes means an integrated system of underground and overhead
piping designed to provide fire protection for a building or structure. The
installation includes one or more automatic water supplies. The portion of the
sprinkler system above-ground is a network of specially sized or hydraulically
designed piping installed in a building, structure, or area generally overhead,
and to which sprinklers are attached in a systematic pattern. The valve
controlling each system riser is located in the sprinkler riser or its supply
piping. Each sprinkler system riser includes a device for actuating an alarm
when the system is in operation. The system is usually activated by heat from a
fire and discharges water over the fire area;
(6) "Hose bibb vacuum breaker" means an
atmospheric vacuum breaker designed to be attached to an outlet having a hose
connection thread;
(7) "Owner"
means the customer of a public water system;
(8) "Pressure vacuum breaker" means a device
which contains a spring loaded check valve and a spring loaded atmospheric vent
which opens when the pressure approaches atmospheric. The unit shall include
two tightly closing shut-off valves located at each end of the device and two
test cocks properly located for testing the device;
(9) "Reduced pressure principle backflow
preventer" (RPD) means a device containing within its structure a minimum of
two independently acting, approved check valves, together with an automatically
operating pressure differential relief valve located between the two check
valves. The first check valve reduces the system pressure a predetermined
amount so that during normal flow and a cessation of normal flow the pressure
between the checks shall be less than the system pressure. In case of leakage
of either check valve, the differential relief valve, by discharging to
atmosphere, shall operate to maintain the pressure between the checks less than
the system pressure. The unit shall include tightly closing shut-off valves
located at each end of the device and each device shall be fitted with properly
located test cocks;
(10) "Siamese
connection" means an inlet equipped with one or more couplings to which a fire
hose can be attached and through which water can be delivered by a fire
department pumper to a sprinkler system; and
(11) "Toxic or objectionable substance" means
any compound which could affect the public health, the potability, or the
aesthetic quality of the water.
(b)
Air Gap. An air gap is
required between all potable water lines and equipment or systems which may be
subject to contamination.
(c)
Reduced pressure principle backflow preventer.
(1) A reduced pressure principle backflow
preventer (RPD) is required on a line to all facilities where toxic or
objectionable substances are used in addition to the required air gap, vacuum
breaker or RPD on individual pieces of equipment unless the public water system
has determined that an RPD is not necessary. Where such substances are used in
a specific area, an RPD on the line to that area may be used in place of the
RPD on the line to the facility.
(2) The owner shall install a reduced
pressure principle backflow preventer (RPD) or an air gap in the following
instances:
(A) On a line to fire sprinkler
systems (including tanks) where chemicals are added or to foam fire fighting
systems;
(B) On a line to
pressurized water systems on ships;
(C) On a line used to supply car wash
facilities where pressure is boosted;
(D) On a line to irrigation or lawn sprinkler
systems where chemicals are added;
(E) On a line to all boiler systems where
chemicals are added;
(F) On a line
to heat exchangers where chemicals are added;
(G) On a line to solar heating systems where
chemicals are added;
(H) On a line
to plating tanks or areas. No potable water use will be allowed downstream of
the device pursuant to section 19-13-B38a(e)(2) of the Regulations of
Connecticut State Agencies.
(3) Unless otherwise required by sections
19-13-B38a(b) or 19-13-B38a(c) of the Regulations of Connecticut State
Agencies, the owner shall install either an RPD or an air vent type backflow
preventer or an air gap in the following instances:
(A) Water supply lines to all boiler systems
where chemicals are not added;
(B)
Water supply lines to carbonators for beverage machines, water conditioning
systems, and commercial ice making equipment;
(C) Water supply lines connected to solar
heating systems where chemicals are not added and heat exchangers where
chemicals are not added;
(D) Water
supply lines to storage tanks used for fire protection where chemicals are not
added.
(d)
Double Check Valve Assembly. The owner shall install a double
check valve assembly (DCVA) on public water supply lines to fire sprinkler
systems with siamese connections unless chemicals are added to the fire
sprinkler system. Where chemicals are added to such systems, the owner shall
install an RPD pursuant to Section
19-13-B38a(c)(2)(A)
of the Regulations of Connecticut State Agencies. An owner may install an RPD
instead of a DCVA on public water supply lines to fire sprinkler systems with
siamese connections.
(e)
Vacuum breaker. The owner shall install either an atmospheric
vacuum breaker or a pressure vacuum breaker or an air gap in the following
instances:
(1) Irrigation or lawn sprinkler
systems where chemicals are not added;
(2) Flush valve toilets;
(3) Inlets which are or may become submerged,
except where an RPD is required pursuant to section
19-13-B38a(c)(2)
of the Regulations of Connecticut State Agencies;
(4) Hemodialysis units;
(5) At marinas and docks on all hose bibbs or
other outlets to which a hose may be connected.
(f)
Installation and
maintenance. The devices required by section
19-13-B38a
of the Regulations of Connecticut State Agencies shall be purchased, owned,
installed, and maintained by the owner in compliance with the following
conditions:
(1) New devices shall conform to
the revision of American Water Works Association Standard C510, C511 or the
revision of the applicable standard of the American Society of Sanitary
Engineering in effect at the time of building permit application.
(2) There shall be no connection made for
potable water use downstream of an RPD and upstream of the equipment or systems
subject to contamination except where the device is installed on the service
line and the required air gap, vacuum breaker, or RPD is provided on all
individual pieces of equipment.
(3)
Each RPD, DCVA and pressure vacuum breaker shall be located in a room or
structure that is well lighted, properly drained, and not subject to flooding.
These devices shall be easily accessible for repair, testing and
inspection.
(4) There shall not be
any bypass around a device without appropriate protection as required by
Section
19-13-B38a
of the Regulations of Connecticut State Agencies.
(5) If an RPD or DCVA cannot be removed from
service for maintenance and testing during normal working hours, then a second
device of the same type shall be installed in parallel so as to permit
inspection and repair of either unit.
(6) The owner shall notify the public water
system prior to the installation of any RPD, DCVA or pressure vacuum breaker
required by Section
19-13-B38a
of the Regulations of Connecticut State Agencies. Immediately after
installation of such devices, the owner shall arrange for the public water
system to have each device tested by a person who has met the requirements of
Section
25-32-11(e)
of the Regulations of Connecticut State Agencies.
(7) The public water system shall have each
RPD, DCVA and pressure vacuum breaker tested annually and shall maintain
records of the test. Any malfunctioning device shall be promptly restored to
proper operating condition by the owner. A summary of the results shall be
forwarded to the Department of Public Health as a part of the annual cross
connection survey report. All tests must be performed by a person who has met
the requirements of Section
25-32-11(e)
of the Regulations of Connecticut State Agencies.
(8) Atmospheric vacuum breakers shall be
located beyond the last control valve prior to the first outlet. All vacuum
breakers shall be installed at an elevation higher than any outlet according to
manufacturer's instructions.
(9) An
atmospheric vacuum breaker shall be installed so that it is not subject to
backpressure or continuous operating pressure of more than twelve (12) hours
duration. Where vacuum breakers are to be installed under section
19-13-B38a(d)
of the Regulations of Connecticut State Agencies and a continuous operating
pressure exists, a pressure vacuum breaker shall be used.
(10) An atmospheric vacuum breaker shall be
installed in such a fashion that it will not be subject to corrosion which will
render it inoperative.
(11) The
owner is responsible for complying with all building, plumbing, fire safety or
other applicable codes, regulations or requirements.
(g)
Civil Penalties.
(1) Notice of violation. When the
Commissioner determines that a violation of Section
19-13-B38a(d)
of the Regulations of Connecticut State Agencies has occurred or is occurring,
the commissioner may so notify the violator and may impose a civil penalty in
accordance with this subsection if compliance is not achieved by the date
specified in the notice of violation.
(2) Appeals. Within twenty days (20) after
such notice is sent by the commissioner, an owner in receipt of a notice of
violation issued pursuant to this subsection may petition the commissioner in
writing, by U.S. mail, certified or registered, postage prepaid, return receipt
requested, for an opportunity to contest the determination that a violation
occurred, the determination a violation has not been corrected, the initial
date of the imposition of the penalty, and the imposition of a
penalty.
(3) Penalty. Failure to
install a device required pursuant to Section
19-13-B38a(d)
of the Regulations of Connecticut State Agencies shall result in a penalty of
not more than $2000.