Connecticut Administrative Code
Title 16 - Public Service Companies
11 - Gas Companies Operating Within the State of Connecticut
Part III - QUALITY CONTROLEquipment, Standards, Records and Reports
Construction and Operation of Plant
Section 16-11-41 - Services
Universal Citation: CT Reg of State Agencies 16-11-41
Current through September 9, 2024
(a) Regulators. (A device for reducing and controlling pressures between the service and house piping)
(1) Any customer's service being supplied
through a customer service pressure regulator shall be protected by a suitable
safety device to prevent the development of pressures in excess of two pounds
per square inch gauge.
(2) Provision
shall be made for the venting of the diaphragms of service pressure regulators
and pressure relief devices to the outside atmosphere. The vent shall be of a
size no smaller than the connection provided by the manufacturer and so
installed as to relieve the entire capacity of the relieving device. Such vent
or vents shall terminate outside buildings, pits and confined spaces in
rain-proof fittings and shall be installed with due regard to hazards to life
and property by the venting of gas into the atmosphere.
(3) All service pressure regulators installed
on the customer's premises shall be maintained in proper working order and
shall be periodically inspected in place, preferably at the time of removal of
the meter for periodic testing. The inspection shall consist of external
examination of the regulator, its piping, seal, vent line and operating
condition.
(b) Shutoffs.
(1) All services
entering a building shall be provided with a shutoff inside of the building and
ahead of the meter. Where a service pressure regulator is part of the metering
installation, the shutoff shall be located upstream of the other gas service
fittings within the building.
(2) A
shutoff shall be installed at the curb or property line on all gas services
supplying gas to a theater, church, school, factory or other building where
large numbers of persons assemble and on all gas services where the inlet
pressure to the service is in excess of two pounds per square inch gauge. In
the case of an outside meter or regulator installation, subsection (c) of
section
16-11-22 shall
apply.
(3) Shutoffs may be either a
cock or a valve and shall be accessible and maintained in proper working
order.
(c) Installation of services.
(1)
The gas company may furnish and install, but shall maintain free of charge, a
gas service from the gas main adjacent to the customer's premises to the
customer's property line or curb when in its judgment the cost of installation
is reasonable and the use of gas is sufficient to warrant it.
(2) While the service connections from the
property line to the customer's metering equipment shall ordinarily be
installed at the expense of the customer and shall be maintained by the
company, the company may furnish such service connections in whole or in part
when, in its judgment, the cost of installation is reasonable and the use of
gas is sufficient to warrant it.
Disclaimer: These regulations may not be the most recent version. Connecticut may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.