8 CCR 1507-60 - RULES FOR FIRE SUPPRESSION PONDS
Section 4 - CRITERIA FOR EVALUATING POTENTIAL FIRE SUPPRESSION PONDS - ACCESSIBILITY BY FIREFIGHTING ENTITIES
Current through Register Vol. 47, No. 5, March 10, 2024
4.1 This section provides the criteria to comply with section 37-82-107(5)(a)(I), C.R.S., which requires that a Fire Suppression Pond "Be readily accessible by a fire protection district, fire authority, fire department, or other firefighting entity". Proposed Fire Suppression Ponds shall be accessible by ground fire apparatus or by rotary wing firefighting aircraft, or both.
4.2 General Design and Accessibility Criteria for All Proposed Fire Suppression Ponds:
4.3 Written Landowner Approval:
4.4 A Proposed Fire Suppression Pond identified by a board of county commissioners for Ground Resource access must meet the following additional minimum criteria:
4.5 A Proposed Fire Suppression Pond identified by a board of county commissioners for Aviation Resources access must meet the following additional minimum criteria:
Distance from perimeter of pond |
Height of Obstacle |
80' |
10' |
160' |
20' |
240' |
30' |
320' |
40' |