Code of Colorado Regulations
1200 - Department of Agriculture
1202 - Inspection and Consumer Services Division
8 CCR 1202-5 - STORAGE AND HANDLING OF ANHYDROUS AMMONIA
Section 4 - LOCATION OF ANHYDROUS AMMONIA SYSTEMS
Universal Citation: 8 CO Code Regs 1202-5 ยง 4
Current through Register Vol. 47, No. 17, September 10, 2024
4.1. Location of Containers
4.1.1.
Consideration shall be given to the physiological effects of ammonia as well as
to adjacent fire hazards in selecting the location for a storage container.
Containers shall be located outside of buildings or in buildings or sections
thereof approved for this purpose.
4.1.2. Containers shall be located at least
50 feet from a dug well or other sources of potable water supply, unless the
container is a part of a water treatment installation.
4.1.3. The location of permanent storage
containers shall be outside densely populated areas, unless the location has
been approved in writing by the appropriate local governing body.
4.1.4. Container locations shall comply with
the following table:
Normal Capacity of |
Minimum Distances (feet) from Container to: |
||
Container (Gallons) |
Line of Adjoining Property Which may be Built Upon, Highways & Mainline of Railroad |
Place of Public Assembly |
Institution Occupancy |
Over 500 to 2,000 |
25 |
150 |
250 |
Over 2,000 to 30,000 |
50 |
300 |
500 |
Over 30,000 to 100,000 |
50 |
450 |
750 |
Over 100,000 |
50 |
600 |
1,000 |
Location approval required from Department within 30 days from notification. |
4.1.5. Storage areas shall be kept free of
readily ignitable materials such as waste, weeds and long dry grass.
Disclaimer: These regulations may not be the most recent version. Colorado may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.