Current through Register Vol. 47, No. 17, September 10, 2024
2.1.
Painting of Containers
2.1.1.
Above-ground uninsulated containers shall have a reflective surface maintained
in good condition. White is recommended for painted surfaces, but other light
reflecting colors are acceptable.
2.2.
Electrical Equipment and
Wiring
2.2.1. Where concentrations of
ammonia in air in excess of 16% by volume are likely to be encountered,
electrical equipment and wiring shall be of a type specified by and be
installed in accordance with National Electrical Code, NFPA 70 (ANSI-C1), for
Class I, Group D locations.
2.3.
Marking on Containers and Systems
other than DOT Containers
2.3.1. System
nameplates, when required, shall be permanently attached to the system so as to
be readily accessible for inspection and shall include markings as prescribed
in 2.3.2.
2.3.2. Each container or
system covered in Sections 7, 9, 10 and 11 shall be marked as follows:
2.3.2.1. With a marking identifying
compliance with the Rules of the code under which the container is
constructed.
2.3.2.2. With a
notation on the container and system nameplate when the system is designed for
underground installation.
2.3.2.3.
With the date of fabrication and the name and address of the supplier of the
container or the trade name of the container.
2.3.2.4. With the water capacity of the
container in pounds at 600F or gallons, U.S. standard.
2.3.2.5. With the design pressure in pounds
per square inch gauge.
2.3.2.6.
With the wall thickness of the shell and heads.
2.3.2.7. With markings indicating the maximum
level to which the container may be filled with liquid anhydrous ammonia at
temperatures between 200F and 1000F except on containers provided with fixed
maximum level indicators, such as fixed length dip tubes, or containers that
are filled by weight.
2.3.2.8. With
the outside surface area in square feet.
2.3.2.9. With minimum temperature in
Fahrenheit for which the container is designed.
2.3.2.10. Marking as specified on containers
shall be on the container itself or on a nameplate permanently affixed
thereto.
2.3.3. All main
operating valves on permanently installed containers having a capacity of over
three thousand water gallons shall be identified to show whether the valve is
in liquid or vapor service. The recommended method of identification may be
legend or color code as specified in 2.3.3.1 or 2.3.3.2.
2.3.3.1. Legend: The legend liquid (or liquid
valve), vapor (or vapor valve), as appropriate, shall be placed on or within
twelve inches of the valve by means of a stencil tag, or decal.
2.3.3.2. Color code: Liquid valves shall be
painted orange and vapor valves shall be painted yellow. The legend
orange-liquid, yellow-vapor shall be displayed in one or more conspicuous
places at each permanent storage location. The legend shall have letters at
least two inches high and shall be placed against a contrasting
background.
2.4.
Container Appurtenances
2.4.1. All appurtenances shall be designed
for not less than the maximum working pressure of that portion of the system on
which they are installed.
2.4.1.1. All
appurtenances shall be fabricated from materials proved suitable for anhydrous
ammonia service.
2.4.1.2. Each
valve and appurtenance shall be designed for not less than the maximum pressure
to which the valve and appurtenance will be subjected.
2.4.1.3. Each valve that could be subjected
to container pressures shall have a rated working pressure of at least 250
psig.
2.4.1.4. Connections to
containers shall be limited to liquid-level gauges, emergency shutoff valves,
pressure gauges, vapor-relief valves, liquid lines, vapor lines, and
thermometers.
2.4.2. All
connections to containers except safety relief devices, gauging devices, or
those fitted with a No. 54 drill size orifice shall have shut-off valves
located as close to the container as practicable.
2.4.3. The emergency shutoff valve shall be
placed in the liquid line internally or externally to the container.
2.4.3.1. If an external valve is used, the
valve shall be located after the manual shutoff valve but as close to the
opening of the container as possible.
2.4.3.2. The emergency shutoff valve shall
work properly from a remote location or when activated at the valve.
2.4.4. Excess flow valves where
required by these Rules shall close automatically at the rated flows of vapor
or liquid as specified by the manufacturer. The connections and line including
valves and fittings being protected by an excess flow valve shall have a
greater capacity than the rated flow of the excess flow valve.
2.4.5. Liquid level gauging devices that
require bleeding of the product to the atmosphere and which are so constructed
that outward flow will not exceed that passed by a No. 54 drill size opening
need not be equipped with excess flow valves.
2.4.6. Openings from containers or through
fittings attached directly on containers to which pressure gauge connections
are made need not be equipped with excess flow valves if such openings are not
larger than No. 54 drill size.
2.4.7. Excess flow and back pressure check
valves where required by these Rules shall be located inside of the container
or at a point outside as close as practicable to where the line enters the
container. In the latter case, installation shall be made in such manner that
any undue stress beyond the excess flow or back pressure check valve will not
cause breakage between the container and the valve.
2.4.8. Excess flow valves shall be designed
with a by-pass, not to exceed a No. 60 drill size opening to allow equalization
of pressures.
2.4.9. Shut-off
valves provided with an excess flow valve shall be designed for proper
installation in a container connection so that the excess flow valve will close
should the shut-off valve break.
2.4.10. All excess flow valves shall be
plainly and permanently marked with the name or trademark of the manufacturer,
the catalog number, and the rated capacity.
2.4.11. Each liquid connection used to fill a
permanent storage container shall be fitted with a backflow check
valve.
2.4.12. All appurtenances to
any permanent storage container shall be protected from tampering and
mechanical damage, including damage from vehicles. Each manually controlled
valve that, if open, would allow ammonia to be transferred or released, shall
be kept locked when unattended and during nonbusiness hours.
2.5.
Piping, Tubing and
Fittings
2.5.1. All piping, tubing and
fittings shall be made of material suitable for anhydrous ammonia
service.
2.5.2. All piping, tubing
and fittings shall be designed for a pressure not less than the maximum
pressure to which they may be subjected in service.
2.5.3. All piping shall be well supported and
provision shall be made for expansion and contraction.
2.5.4. Piping used on non-refrigerated
systems shall be at least ASTM A-53 Grade B Electric Resistance Welded and
Electric Flash Welded Pipe or equal. Such pipe shall be at least Schedule 40
when joints are welded, or welded and flanged. Such pipe shall be at least
Schedule 80 when joints are threaded. Brass, copper, or galvanized steel pipe
or tubing shall not be used.
2.5.5.
All metal flexible connections for permanent installations shall have a minimum
working pressure of 250 psig (safety factor of 4). For temporary installations,
hose meeting the requirement of 2.6 may be used.
2.5.6. Cast iron fittings shall not be used
but this shall not prohibit the use of fittings made specifically for ammonia
service of malleable or nodular iron such as specification ASTM A47 or ASTM
A395.
2.5.7. Provisions shall be
made for expansion, contraction, jarring, vibration, and for
settling.
2.5.8. Adequate
provisions shall be made to protect all exposed piping from physical damage
that might result from moving machinery, the presence of automobiles or trucks,
or any other undue strain that may be placed upon the piping.
2.5.9. Joint compounds shall be resistant to
ammonia.
2.5.10. After assembly,
all piping and tubing shall be tested and proved to be free from leaks at a
pressure not less than the normal operating pressure of the system.
2.6.
Hose
Specification
2.6.1. Hoses used in
ammonia service and subject to container pressure shall conform to the
specification set forth in Appendix B of this Rule, which are based on The
Rubber Manufacturers Association and The Fertilizer Institute "Hose
Specifications for Anhydrous Ammonia".
2.6.2. Hose subject to container pressure
shall be designed for a minimum working pressure of 350 psig and a minimum
burst pressure of 1750 psig. Hose assemblies, when made up, shall be capable of
withstanding a test pressure of 500 psig.
2.6.3. Hose and hose connections located on
the low pressure side of flow control or pressure reducing valves on devices
discharging to atmospheric pressure shall be designed for the maximum low side
working pressure. All connections shall be designed, constructed, and installed
so that there will be no leakage when connected.
2.6.4. Where liquid transfer hose is not
drained of liquid upon completion of transfer operations, such hose shall be
equipped with an approved shut-off valve at the discharge end. Provision shall
be made to prevent excessive hydrostatic pressure in the hose. (See Rule
2.7.16.).
2.6.5. On all hose
one-half inch O.D. and larger, used for the transfer of anhydrous ammonia
liquid or vapor, there shall be etched, cast, or impressed at five-foot
intervals the following information:
2.6.5.1.
"Anhydrous Ammonia";
2.6.5.2. xxx
psig (Maximum working pressure);
2.6.5.3. Manufacturer's Name or
Trademark;
2.6.5.4. Year of
Manufacture; and
2.6.5.5. The date
specified by the manufacturer on which the hose is to be removed from service
(Manufacturer's removal date).
2.6.6. Each hose shall be replaced before or
upon the expiration of the manufacturer's removal date.
2.6.7. A hose shall be removed from service
prior to the manufacturer's removal date if a visual examination reveals any of
the following:
2.6.7.1. Illegibility of any of
the markings required in subsection 2.6.5;
2.6.7.2. Cuts exposing reinforcing
fabric;
2.6.7.3. Soft spots or
bulges in the hose;
2.6.7.4. A
blistering or loose outer covering;
2.6.7.5. Kinking or flattening;
2.6.7.6. Stretch marks;
2.6.7.7. Slippage at any coupling;
or
2.6.7.8. Any other damage that
could compromise the integrity of the safe use of the hose.
2.7.
Safety Relief
Devices
2.7.1. Every container used in
systems covered by Sections 7, 9, 10 and 11 shall be provided with one or more
safety relief valves of the spring-loaded or equivalent type. The discharge
from safety relief valves shall be vented away from the container, upward and
unobstructed to the atmosphere. All safety relief valve discharge openings
shall have suitable rain caps that will allow free discharge of the vapor and
prevent the entrance of water. Provision shall be made for draining condensate
which may accumulate. The rate of the discharge shall be in accordance with the
provisions of Appendix A of this Rule.
2.7.2. Container safety relief valves shall
be set to start-to-discharge as follows, based on the design pressure of the
container:
Containers
|
Minimum
|
Maximum*
|
ASME-U-68, U-69
|
110%
|
125%
|
ASME-U-200, U-201
|
95%
|
100%
|
ASME 1952, 1956, 1959, 1962, 1965, 1968 or
1971
|
95%
|
100%
|
API-ASME
|
95%
|
100%
|
U.S. Coast Guard
|
[As required by USCG regulations]
|
DOT
|
[As required by DOT Regulations]
|
* NOTE: A RELIEF VALVE MANUFACTURER'S TOLERANCE OF PLUS 10%
IS PERMITTED.
2.7.3. Safety
relief devices used in systems covered by Sections 7, 9, 10 and 11 shall be
constructed to discharge at not less than the rates required in 2.7.1 before
the pressure is in excess of 120% (not including the 10% tolerance referred to
in 2.7.2) of the maximum permitted start-to-discharge pressure setting of the
device.
2.7.4. Safety relief valves
shall be so arranged to minimize the possibility of tampering. If the pressure
setting adjustment is external, the relief valves shall be provided with means
for sealing the adjustment.
2.7.5.
Shut-off valves shall not be installed between the safety relief valves and the
containers or systems described in Sections 7, 9, 10 and 11, except that a
shut-off valve may be used where the arrangement of this valve is such as
always to afford required capacity flow through the relief valves.
NOTE: The above exception is made to cover such cases as a
three-way valve installed under two safety relief valves, each of which has the
required rate of discharge and is so installed as to allow either of the safety
relief valves to be closed off, but does not allow both safety valves to be
closed off at the same time. Another exception to this may be where two
separate relief valves are installed with individual shut-off valves. In this
case, the two shut-off valve stems shall be mechanically interconnected in a
manner which will allow full required flow of one safety relief valve at all
times. Still another exception is a safety relief valve manifold which allows
one valve of two, three, four or more to be closed off and the remaining valve
or valves will provide not less than the rate of discharge shown on the
manifold nameplate.
2.7.6.
Safety relief valves shall have direct communication with the vapor space of
the container.
2.7.7. Each safety
relief valve used with systems described in Sections 7, 9, 10 and 11 shall be
plainly and permanently marked as follows:
2.7.7.1. With the letters "AA" or the symbol
"NH3".
2.7.7.2. The pressure in
pounds per square inch gauge (psig) at which the valve is set to
start-to-discharge.
2.7.7.3. The
rate of discharge of the valve in cubic feet per minute of air at 60ºF and
atmospheric pressure (14.7 psia).
2.7.7.4. The manufacturer's name and catalog
number.
For example, a safety relief valve marked AA-250-4200 (air)
would mean that this valve is suitable for use on an anhydrous ammonia
container; that it is set to start-to-discharge at 250 psig; and that its rate
of discharge (see Sections 2.7.1 , 2.7.2 , and 2.7.3) is 4200 cubic feet per
minute of air.
2.7.8. Each pressure-relief valve shall be
manufactured for use with anhydrous ammonia and be installed, maintained, and
replaced according to the manufacturer's instructions.
2.7.9. Unless otherwise specified by the
manufacturer, a pressure-relief valve shall not be used for more than five
years after the date of manufacture of the pressure relief device.
2.7.10. Each safety valve shall be replaced
if the valve meets any of the following conditions:
2.7.10.1. Fails to meet applicable
requirements;
2.7.10.2. Shows
evidence of damage, corrosion, or foreign matter; or
2.7.10.3. Does not have functional weep holes
that permit moisture to escape.
2.7.11. If moisture accumulation could occur
in a vent, suitable provision shall be made to drain the moisture from the
vent.
2.7.12. The flow capacity of
the safety relief valve shall not be restricted by any connection to it on
either the upstream or downstream side.
2.7.13. Vent pipes or tubing used to channel
releases from safety relief valves shall not be restricted or smaller in size
than the safety relief valve outlet connection.
2.7.14. Vent pipes may be connected and
channeled into a common header if the cross-sectional area of the header is at
least equal to the sum of the cross-sectional areas of each of the individual
vent pipes.
2.7.15. The
manufacturer or supplier of a safety relief valve manifold shall publish
complete data showing the flow rating through the combined assembly of the
manifold with safety relief valves installed. The manifold flow rating shall be
determined by testing the manifold with all but one valve discharging. If one
or more openings have restrictions not present in the remaining openings, the
restricted opening or openings or those having the lowest flow shall be used to
establish the flow rate marked on the manifold nameplate. The marking shall be
similar to that required in 2.7.7 for individual valves.
2.7.16. A hydrostatic relief valve shall be
installed between each pair of valves in the liquid ammonia piping or hose
where liquid may be trapped so as to release into the atmosphere at a safe
location.
2.7.17. Discharge from
safety relief devices shall not terminate in or beneath any building.
2.8.
Liquid Level Gauging
Device
2.8.1. Each container except
those filled by weight shall be equipped with an approved liquid level gauging
device.
2.8.2. All gauging devices
shall be arranged so that the maximum liquid level to which the container is
filled is readily determined (See 2.3.2.7).
2.8.3. Gauging devices that require bleeding
of the product to the atmosphere such as the rotary tube, fixed tube, and slip
tube devices, shall be designed so that the maximum opening of the bleed valve
is not larger than No. 54 drill size unless provided with an excess flow valve.
(This requirement does not apply to farm vehicles used for the application of
ammonia, as covered in Section 11.)
2.8.4. Gauging devices shall have a design
pressure equal to or greater than the design pressure of the container on which
they are installed.
2.8.5. Fixed
liquid level gauges shall be so designed that the maximum volume of the
container filled by liquid shall not exceed 85% of its water capacity. The
coupling into which the fixed liquid level gauge is threaded must be placed at
the 85% level of the container. If located elsewhere, the dip tube of this
gauge must be installed in such a manner that it cannot be readily
removed.
2.8.6. Gauge glasses of
the columnar type shall be restricted to stationary storage installations. They
shall be equipped with shut-off valves having metallic hand wheels, with
excess-flow valves, and with extra heavy glass adequately protected with a
metal housing applied by the gauge manufacturer. They shall be shielded against
the direct rays of the sun.