Section 5590 - Spacing (Shell-to-Shell) Between Aboveground Tanks

Universal Citation: 8 CA Code of Regs 5590

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) The distance between any two flammable or combustible liquid storage tanks shall not be less than three feet.

(b) Except as provided in (c), the distance between any two adjacent tanks any one of which stores Category 1, 2, 3 or 4 flammable liquids shall not be less than one-sixth the sum of their diameters, except when the diameter of one tank is less than one-half the diameter of the adjacent tank, the distance between the two tanks shall not be less than one-half the diameter of the smaller tank. Tanks used only for storing liquids with a flashpoint greater than 199.4 °F (93 °C) (formerly designated Class IIIB Combustible liquids) may be spaced as provided in (a) unless within a diked area or drainage path for a tank storing a Category 1, 2 or 3 flammable liquid.

(c) Crude petroleum tanks at production facilities in isolated locations having capacities not exceeding 126,000 gallons (3,000 barrels), need not be separated by more than three feet.

(d) For unstable flammable or combustible liquids, the distance between such tanks shall not be less than one-half the sum of their diameters.

(e) When tanks are in a diked area containing Category 1, 2 or 3 flammable liquids, or in the drainage path of Category 1, 2 or 3 flammable liquids, and are compacted in three or more rows or in an irregular pattern, greater spacing or other means shall be provided to make inside tanks accessible for fire fighting purposes.

(f) The minimum separation between a liquefied petroleum gas container and a flammable or combustible liquid storage tank shall be 20 feet, except in the case of flammable or combustible liquid tanks operating at pressures exceeding 2.5 psig or equipped with emergency venting which will permit pressures to exceed 2.5 psig in which case the provisions of (a) and (b) shall apply. Suitable means shall be taken to prevent the accumulation of flammable or combustible liquids under adjacent liquefied petroleum gas containers such as by diversion curbs or grading. When flammable or combustible liquid storage tanks are within a diked area, the liquefied petroleum gas containers shall be outside the diked area and at least 10 feet away from the center line of the wall of the diked area. The foregoing provisions shall not apply when liquefied petroleum gas containers of 125 gallons or less capacity are installed adjacent to fuel oil supply tanks of 550 gallons or less capacity.

1. Amendment of subsections (b) and (e)-(f) and new NOTE filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.