California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 7 - General Industry Safety Orders
Group 20 - Flammable Liquids, Gases and Vapors
Article 145 - Tank Storage
Section 5589 - Installation of Outside Aboveground Tanks

Universal Citation: 8 CA Code of Regs 5589

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Every aboveground tank for the storage of Category 1, 2, 3 or 4 flammable liquids, except those liquids with boil-over characteristics and unstable liquids, operating at pressures not in excess of 2.5 psig and designed with a weak roof-to-shell seam or equipped with emergency venting devices which will not permit pressures to exceed 2.5 psig, shall be located in accordance with Table FL-10.

(1) For the purpose of this Section, a floating roof tank is one which incorporates a pontoon or double deck roof in an open top tank in accordance with API Standard 650, or one which incorporates an internal all-metal (except for seals) floating cover with a fixed metal roof with adequate ventilation at the eaves of the roof. Tanks with internal floating covers incorporating nonmetallic construction, such as plastics, shall be treated as cone roof tanks.

(b) Every aboveground tank for the storage of Category 1, 2, 3 or 4 flammable liquids, except those liquids with boil-over characteristics and unstable flammable or combustible liquids, operating at pressures exceeding 2.5 psig or equipped with emergency venting which will permit pressures to exceed 2.5 psig shall be located in accordance with Table FL-11.

(c) Every aboveground tank for the storage of Category 1, 2, 3 or 4 flammable liquids with boil-over characteristics shall be located in accordance with Table FL-12.

(d) Every aboveground tank for the storage of unstable liquids shall be located in accordance with Table FL-13.

(e) Every aboveground tank for the storage of liquids with a flashpoint greater than 199.4 °F (93 °C) (formerly designated Class IIIB Combustible liquids), excluding unstable liquids, shall be located in accordance with Table FL-14 except when located within a diked area or drainage path for a tank or tanks storing a Category 1, 2 or 3 flammable liquid. When a combustible liquid (formerly designated Class IIIB liquid) storage tank is within the diked area or drainage path for a Category 1, 2 or 3 flammable liquid, (a) or (b) shall apply.

(f) Reference minimum distances for use in Tables FL-10 to FL-13, inclusive.

(g) Where end failure of horizontal pressure tanks and vessels may expose property, the tank shall be placed with the longitudinal axis parallel to the nearest important building.

Table FL-10

Type of TankProtectionMinimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public Way and Shall Be Not Less Than Five (5) FeetMinimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building and Shall Be Not Less Than Five (5) Feet
Floating RoofProtection for Exposures 1/2 times diameter of tank but need not exeed 90 feet 1/6 times diameter of tank but need not exceed 30 feet
NoneDiameter of tank but need not exceed 175 feet 1/6 times diameter of tank but need not exceed 30 feet
Vertical with Weak Roof to Shell SeamApproved foam or inerting system on the tank 1/2 times diameter of tank but need not exceed 90 feet 1/6 times diameter of tank but need not exceed 30 feet
Protection for ExposuresDiameter of tank but need not exceed 175 feet 1/3 times diameter of tank but need not exceed 60 feet
None2 times diameter of tank but need not exceed 350 feet 1/3 times diameter of tank but need not exceed 60 feet
Horizontal and Vertical, with Emergency Relief Venting to Limit Pressures to 2.5 psigApproved inerting system on the tank or approved foam system on vertical tanks 1/2 times Table FL-15 1/2 times Table FL-15
Protection for ExposuresTable FL-15Table FL-15
None2 times Table FL-15Table FL-15

Table FL-11

Type of TankProtectionMinimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public WayMinimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
Any TypeProtection for Exposures1 1/2 times Table FL-15 but shall not be less than 25 feet1 1/2 times Table FL-15 but shall not be less than 25 feet
None3 times Table FL-15 but shall not be less than 50 feet1 1/2 times Table FL-15 but shall not be less than 25 feet

Table FL-12

Type of TankProtectionMinimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public WayMinimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
Floating RoofProtection for Exposures 1/2 times diameter of tank but need not exceed 90 feet 1/6 times diameter of tank but need not exceed 30 feet
NoneDiameter of tank but need not exceed 175 feet 1/6 times diameter of tank but need not exceed 30 feet
Fixed RoofApproved foam or inerting systemDiameter of tank but need not exceed 175 feet 1/3 times diameter of tank but need not exceed 60 feet
Protection for Exposures2 times diameter of tank but need not exceed 350 feet 2/3 times diameter of tank but need not exceed 120 feet
None4 times diameter of tank but need not exceed 350 feet 2/3 times diameter of tank but need not exceed 120 feet

Table FL-13

Type of TankProtectionMinimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public WayMinimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
Horizontal and Vertical Tanks With Emergency Relief Venting to Permit Pressure Not in Excess of 2.5 psigTank protected with any one of the following: Approved water spray, Approved inerting, Approved insulation and refrigeration, Approved barricadeTable FL-15 but not less than 25 feetNot less than 25 feet
Protection for Exposures2 1/2 times Table FL-15 but not less than 50 feetNot less than 50 feet
None5 times Table FL-15 but not less than 100 feetNot less than 100 feet
Horizontal and Vertical Tanks With Emergency Relief Venting to Permit PressureTank protected with any one of the following: Approved water spray, Approved inerting, Approved insulation and refrigeration, Approved barricade2 times Table FL-15 but not less than 50 feetNot less than 50 feet
Protection for Exposures4 times Table FL-15 but not less than 100 feetNot less than 100 feet
None8 times Table FL-15 but not less than 150 feetNot less than 150 feet

Table FL-14

Capacity GallonsMinimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public WayMinimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
12,000 or less55
12,001 to 30,000105
30,001 to 50,0001010
50,001 to 100,0001510
100,001 or more1515

Table FL-15

Capacity Tank GallonsMinimum Distance in Feet From Property Line Which May Be Built Upon, Including the Opposite Side of a Public WayMinimum Distance in Feet From Nearest Side of Any Public Way or From Nearest Important Building
275 or less55
276 to 750105
751 to 12,000155
12,001 to 30,000205
30,001 to 50,0003010
50,001 to 100,0005015
100,001 to 500,0008025
500,001 to 1,000,00010035
1,000,001 to 2,000,00013545
2,000,001 to 3,000,00016555
3,000,001 or more17560

1. Amendment of subsection (e) and Table FL-11 filed 12-19-78; effective thirtieth day thereafter (Register 79, No. 1).
2. Amendment of subsections (a), (b) and (e) and amendment of NOTE filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.