Section 5585.1 - Liquid Level Indicator, Temperature Regulator, Combustible Liquids
Atmospheric tanks used for storing combustible liquids (as defined in Section 5415) heated by internal heating coil/element shall be equipped with a liquid level indicator or equivalent device that displays the liquid level in the tank; or a temperature regulating system. When equipped with a temperature regulating system, the temperature regulating system shall automatically shut off the heat source to the tank before the tank contents reach the ignition temperature. If a liquid level indicator is the sole sensing method, 1) the liquid level indicator shall be affixed to the tank or located elsewhere, such as in a control room, 2) the liquid level indicator shall be monitored when filling or emptying the tank, 3) the location of the internal heating coil/element on the tank shall be clearly indicated.