Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) A listed manual or automatic-closing type hose nozzle valve shall be provided on dispensers used for the dispensing of Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C).
(b) Overhead-type dispensing units shall be provided with a listed automatic-closing type hose nozzle valve without a latch-open device.
(c) Dispensing nozzles used at marine service stations shall be of the automatic-closing type without a latch-open device.
(d) Manual-closing type valves shall be held open manually during dispensing. Automatic-closing type valves may be used in conjunction with an approved latch-open device.
EXCEPTION: Nozzles which are an integral part of a gasoline vapor recovery system, certified by the State Air Resources Board and the State Fire Marshal pursuant to the provisions of Sections 41954 through 41961, inclusive, of the California Health and Safety Codes.
1.
Amendment filed 3-3-77; effective thirtieth day thereafter (Register 77, No.
10).
2. Amendment filed 5-12-83; effective thirtieth day thereafter
(Register 83, No. 20).
3. Amendment of subsection (a) filed
5-5-2014; operative 5-6-2014 pursuant to Government Code section
11343.4(b)(3)
(Register 2014, No. 19).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.