California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 7 - General Industry Safety Orders
Group 20 - Flammable Liquids, Gases and Vapors
Article 138 - Hydrogen
Section 5489 - Electrical Systems
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Electrical wiring and equipment located within 3 feet of a point where connections are regularly made and disconnected, shall be in accordance with the California Electrical Safety Orders for Class I, Group B, Division 1 locations.
(b) Except as provided in (a), electrical wiring and equipment located within 25 feet of a point where connections are regularly made and disconnected or within 25 feet of a liquid hydrogen storage container, shall be in accordance with the California Electrical Safety Orders for Class I, Group B, Division 2 locations. When equipment approved for Class I, Group B atmospheres is not commercially available, the equipment may be purged or ventilated in accordance with NFPA No. 496, Standard for Purged Enclosures for Electrical Equipment in Hazardous Locations, or intrinsically safe, or approved for Class I, Group C atmospheres. This requirement does not apply to electrical equipment which is installed on mobile supply trucks or tank cars from which the storage container is filled. (Title 24, T8-5489)
1. Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).