Section 5434 - Fire Protection
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Except as noted in Section 5436(e) (applying to hardening and tempering tanks), all dip tanks exceeding 150 gallons liquid capacity, or having a liquid surface area exceeding four square feet, shall be protected with automatic extinguishing facilities or covers so designed and installed as to close automatically in case of fire. (See Section 5435.)
(b) Areas in the vicinity of dip tanks shall be provided with portable fire extinguishers suitable for flammable and combustible liquid fires, conforming to Article 157.
(c) Automatic water spray extinguishing systems shall conform to Article 163 and shall be arranged to protect tanks, drain boards and stock over drain boards.
(d) Automatic foam extinguishing systems shall conform to Article 163 and to NFPA No. 111983, NFPA 11A-1983, or NFPA 11B1977 and shall also conform to the following:
(e) Automatic carbon dioxide systems shall conform to Article 162 and shall be arranged to protect both dip tanks and drain boards and unless stock over drain boards is otherwise protected with automatic extinguishing facilities, shall also be arranged to protect such stock.
(f) Dry chemical extinguishing systems shall conform to Article 161 and shall be arranged to protect both dip tanks and drain boards, and unless stock over drain boards is otherwise protected with automatic extinguishing facilities, shall also be arranged to protect such stock.
(g) Automatic closing process tank covers or special extinguishing systems shall be provided for open tanks under 150 gallons capacity or 10 sq. ft. in liquid surface area.
(h) Protection systems shall be provided for tanks 150 gallons capacity and over or 10 sq. ft. in liquid surface area and over. These systems shall be designed to protect the following areas:
1.
Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No.
29).
2. Amendment filed 9-8-81; effective thirtieth day thereafter
(Register 81, No. 37).
3. Editorial correction of subsection (d)
filed 11-9-81; effective thirtieth day thereafter (Register 81, No.
45).
4. Editorial correction of subsection (c) filed 6-30-82
(Register 82, No. 27).
5. Amendment of subsection (d)(2)(A) filed
7-8-85; effective thirtieth day thereafter (Register 85, No. 28).
6.
Amendment of subsections (d) and (f) and new subsection (g) filed 12-5-86;
effective thirtieth day thereafter (Register 86, No.
51).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.