(a)
Location of Arming Room.
(1) During arming
procedures the arming room shall be located and separated from any building or
structure occupied by the public or non-essential personnel the equivalent
distance required by the Table of Distances in Article 114 of these Orders, for
the maximum amount of explosives that will be allowed in the arming room at any
time.
(2) The quantity of
explosives used to determine the distances shall be the maximum amount that
will be allowed in the arming room at any time.
(3) Only authorized and essential personnel
to the operation shall be allowed within the arming room and within the
equivalent distance to occupied structures required by the Table of Distances
for the amount of explosives present.
NOTE: Essential personnel are those individuals
directly involved with the arming, the deployment of charges, transportation
and site clearing to facilitate transportation. Non-essential personnel are all
other individuals.
(b) Arming Room Construction.
(1) Interior of the arming room shall be
finished and equipped to the following minimum requirements:
(A) The walls shall be of a smooth finish
without cracks or crevices with all nails, screws, bolts and nuts countersunk.
Exposed metal or materials capable of emitting sparks shall be covered so as
not to come in contact with packages of explosive materials;
(B) The floors shall be constructed of, or
covered with, a non-sparking material;
(C) The building and arming room shall be
well ventilated, and the ventilation system shall discharge to the outside from
the arming room;
(D) The arming
table shall be constructed of non-sparking, nonconductive
material;
(c)
Arming Room Restrictions.
(1) Heating units
shall be explosion proof, dust-proof and not depend on a combustion process
when properly designed and located. Explosion proof and dust-proof heating
units rated for Class II, Division I, Hazardous Locations, pursuant to Article
59, of the Electrical Safety Orders, may be used inside arming rooms.
(2) Temperature control devices shall be
adequately designed to prevent overheating of arming rooms when explosives are
present.
(3) Lighting fixtures and
all wiring shall meet, or shall be equivalent to the requirements for Class II,
Division I, Hazardous Location, pursuant to Article 59, of the Electrical
Safety Orders, and shall be located a minimum of 5 feet from the explosives.
Mine Safety and Health Administration-permissible portable lighting may be
used.
(4) All electric control
switches, outlet boxes and junction boxes shall be located outside the arming
room.
(5) Smoking, matches, open
flames, or flame or spark producing devices shall not be permitted inside the
arming room.
(6) Flammable and
combustible liquids or flammable compressed gases shall not be used or stored
in the arming room.
(7) Occupancy
of arming room shall be limited to authorized and trained personnel when
explosives are present. Trainees shall be permitted in the arming room under
the direct personal supervision of a licensed avalanche blaster.
(8) The arming room shall not be used for
storage of explosives, detonator systems, or components.
EXCEPTION: A maximum total of 5000 caps and capped
fuses may be stored in the arming room inside a separate Type 2 magazine. The
Type 2 magazine shall be located within 10 feet from an outside exit door at
grade level.
(d)
Arming Room Housekeeping.
(1) The arming room
shall be kept clean and orderly.
(2) Only non-sparking tools and devices shall
be used or stored in the arming room.
(3) Brooms used in the arming room shall be
made of non-sparking materials.
(4)
Sweepings and empty explosive material containers shall be disposed of as
recommended by the manufacturer.
(5) The arming room shall be cleaned and all
explosive materials shall be removed upon completion of daily arming activities
except as provided in the subsection (8) exception. The arming room shall be
cleaned and all explosive materials shall be removed when any repairs are made
to the arming room.
(6) The arming
table or bench shall be cleaned regularly and shall be kept free of any
materials or tools not used in the assembly of the charges.
1. New
section filed 10-10-2007; operative 11-9-2007 (Register 2007, No.
41).
Note: Authority cited: Section
142.3, Labor
Code. Reference: Section
142.3, Labor