California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 7 - General Industry Safety Orders
Group 16 - Control of Hazardous Substances
Article 111 - Fumigation
Section 5223 - Fumigation in Buildings or Rooms Other than Fumigation Vaults or Chambers
Universal Citation: 8 CA Code of Regs 5223
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Whenever any building or section thereof, other than fumigation vaults or chambers, are fumigated with a poisonous gas:
(1) All
cracks, holes, crevices, openings, and apertures in walls, floors, and ceilings
shall be sealed so as to confine the gas to the rooms being
fumigated.
(2) Doors and windows
shall be closed and sealed; and legible warning signs shall be posted at all
entrances or approaches. Signs shall state premises under fumigation and type
of gas used and shall not be removed till fumigation and ventilation are
complete.
(3) Employees releasing
poisonous gases for fumigation shall wear respiratory protection of a type
approved for use in the gas used.
(4) Fumigation of single rooms is forbidden
unless such room constitutes a wing, floor, or other detached or semi-detached
section of a building, or can be effectively sealed off from the remainder of
the building.
(5) When a part of a
building is to be fumigated, all adjoining rooms, including those above and
below, and all other parts of the building or of adjacent buildings into which
the gas may penetrate shall be vacated. Windows in such locations shall be open
during fumigation.
(6) After the
exposure is completed, premises shall be purged of fumigant and the air therein
shall be tested. Employees shall not be allowed to enter the premises, except
to make tests, until the concentration of fumigant is known to be safe.
Employees making tests shall wear respiratory protection approved for use in
the fumigant used.
(7) Purging or
ventilation shall be carried out in such a manner as not to endanger
employees.
(8) Where flammable
fumigants are used, no source of ignition shall be allowed in premises being
fumigated. When part of a building is being fumigated, no source of ignition
shall be allowed in the rooms being fumigated or in adjoining rooms including
those above and below, or in adjacent buildings into which gas may reasonably
be expected to penetrate.
1.
Renumbering of Section
5217 to Section 5223 filed 5-3-78
as procedural and organizational; effective upon filing (Register 78, No.
18).
2. Change without regulatory effect amending subsections
(a)(2)-(3) filed 12-19-2002 pursuant to section
100, title 1, California Code of
Regulations (Register 2002, No. 51).
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.