Universal Citation: 8 CA Code of Regs C
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
Rooms used for audiometric testing shall not have background sound pressure levels exceeding those in Table C-1 when measured by equipment conforming at least to the Type 2 requirements of ANSI S 1.4-1971 (R1976), and to the Class II requirements of ANSI S 1.11-1971 (R1976).
Table C-1 |
|||||
Maximum Allowable Octave-Band Sound Pressure Levels for Audiometric Test Rooms | |||||
Octave-band center frequency (Hz) .......................... | 500 | 1000 | 2000 | 4000 | 8000 |
Sound pressure level (dB) .......................... | 40 | 40 | 47 | 57 | 62 |
1. Amendment filed 10-3-83; effective thirtieth day thereafter (Register 83, No. 41).
Note: Authority cited and Reference: Section 142.3, Labor Code.
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.