California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 7 - General Industry Safety Orders
Group 10 - Gas Systems for Welding and Cutting
Article 82 - Stationary Automatic Acetylene Generators
Section 4811 - Generator Escape or Relief Pipes
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Each generating chamber shall be provided with an escape or relief pipe, installed without traps so that any condensate will drain back into the chamber.
(b) All relief pipes shall be carried to a suitable point outside the building and shall terminate in a suitable hood or bend located at least 12 feet above the ground and at least three feet from combustible construction. Each generator shall be provided with a vent pipe of Schedule 40 galvanized iron or steel, or equivalent.
(c) Generating chamber relief pipes shall not be interconnected but shall be led separately to the outside air.
1.
Amendment of subsection (b) filed 5-16-75; effective thirtieth day thereafter
(Register 75, No. 20).
2. Amendment filed 7-16-76; effective
thirtieth day thereafter (Register 76, No. 29).
3. Amendment of
subsection (b) filed 9-19-80; effective thirtieth day thereafter (Register 80,
No. 38).
4. Amendment of subsection (c) filed 6-12-87; operative
7-12-87 (Register 87, No. 26).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.