California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 7 - General Industry Safety Orders
Group 10 - Gas Systems for Welding and Cutting
Article 82 - Stationary Automatic Acetylene Generators
Section 4805 - Inside Generator Rooms or Compartments

Universal Citation: 8 CA Code of Regs 4805

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Acetylene Generators shall not be installed in buildings exceeding one story in height, unless they are installed on the top floor or roof.

(b) Generators installed inside buildings shall be enclosed in a separate room. The walls, partitions, floors, and ceilings of inside general rooms shall be of construction having a fire-resistance rating of at least one-hour.

The walls or partitions shall be continuous from floor to ceiling and shall be securely anchored. At least one wall of the room shall be an external wall.

(c) Openings from an inside generator room to other parts of the building shall be protected by a swinging type, self-closing fire door for a Class B opening and having a rating of a least 1 hour. Windows in partitions shall be wired glass and approved metal frames with fixed sash. Installation shall be in accordance with the Standard for the Installation of Fire doors and Windows, NFPA 80-1970.

(d) A portion of the exterior walls or roof equal to not less than 10 percent of combined areas of the enclosing walls and roof shall be of light, noncombustible material, preferably single-strength glass.

1. Amendment of subsection (c) filed 3-2-76; effective thirtieth day thereafter (Register 76, No. 10).
2. Amendment filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
3. Amendment filed 6-12-87; operative 7-12-87 (Register 87, No. 26).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.