Section 3071 - Operation, Operating Devices and Control Equipment
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Types of Operating Devices.
EXCEPTIONS:
(b) Operation. Operation shall conform to the requirements of sections 3040(a)(4), (a)(5), (a)(6), (a)(7) and (a)(8).
(c) Leveling Devices and Truck-Zoning Devices.
(d) Electrical Protective Devices. In addition to the terminal stopping devices required by section 3070, the following electrical protective devices shall be provided and shall conform to the requirements of section 3040(b), except that their operation shall cause the electrical power to be removed from all control valves and from the pump motor.
EXCEPTION: Devices (4), (5), and (6) need not remove the power within the leveling zones.
(e) Requirements for Electrical Equipment and Wiring. All electrical equipment and wiring shall comply with the provisions of CCR, Title 24, Part 3, Article 620.
(f) Installation of Condensers or Devices to Make Electrical Protective Devices Inoperative. The installation of condensers or other devices to make electrical protective devices inoperative shall conform to section 3040(d).
(g) Control and Operating Circuit Requirements. The design and installation of the control and operating circuits shall conform to the following requirements:
(h) Load-Weighing Devices on Passenger Elevators. Load-weighing devices which will stop the elevator while running shall not be installed in connection with passenger elevators. They may be installed to prevent the elevator from leaving a floor but the setting shall be for a load not more than that which would actuate the relief valve.
(i) Car Emergency Signal. Elevators which are operated at any time without a designated operator shall be provided with an emergency signal conforming to the requirements of section 3041(a).
(j) Load Test Required. Every hydraulic elevator installed hereafter shall be field tested before a permit to operate is issued, and again at intervals not to exceed five (5) years.
EXCEPTION to Section 3071(j)(1)(A)1:
For elevators installed prior to 3-21-70 the Division may accept a greater percentage of the actual speed.
(k) Out-of-Service Requirements.
Note: To facilitate reactivation of the elevator, the car should be landed at least 2 feet above the bottom terminal.
(l) Operation of Elevators Under Fire or Other Emergency Conditions.
(m) Loss of Pressure Device. A pressure switch or other means shall be provided to prevent the liquid in the cylinder or plunger from returning to the tank through an open valve in the event the weight of the platform is removed from the cylinder or plunger.
(n) Photoelectric Tube By-Pass Switch. Elevators equipped with photoelectric tube devices which control the closing of automatic, power-operated car or hoistway doors, or both, shall conform to the requirements of section 3041(b).
(o) Medical Emergency Elevators. All buildings and structures constructed after the effective date of this order that are provided with one or more passenger elevators shall conform to the requirements of section 3041(e).
(Title 24, Part 7, Section 7-3071)
1. New subsection (l) filed 9-5-75; effective thirtieth day thereafter (Register 75, No. 36).
2. New subsection (m) filed 11-24-76; effective thirtieth day thereafter (Register 76, No. 48).
3. Amendment of subsections (a), (b) and (k) filed 6-23-77; effective thirtieth day thereafter (Register 77, No. 26).
4. Amendment of subsection (c); repealer and new subsection (l) filed 12-22-78; effective thirtieth day thereafter (Register 79, No. 1).
5. Amendment filed 12-8-86; effective thirtieth day thereafter (Register 86, No. 50).
6. New subsections (n) and (o) approved by the Building Standards Commission on 5-24-91 and filed 6-12-91; operative 7-12-91 (Register 91, No. 34).
7. Amendment of subsections (e) and (o) and repealer of subsections (e)(1)-(2) filed 6-29-94; operative 7-29-94 (Register 94, No. 26).
8. Redesignation of subsections (j)(1)-(j)(1)(E), amendment of subsection (j)(1)(A)1 EXCEPTION, subsections (j)(1)(B), (D) and (E) and new subsections (j)(2)-(j)(2)3 filed 12-6-94; operative 1-5-95 (Register 94, No. 49).
9. Editorial correction of subsections (a)(2) EXCEPTION 2 and (j)(2) (Register 95, No. 32).
10. Amendment of subsections (j)(1)(A) and (j)(1)(C) and deletion of subsection (j)(1)(E) approved by the Building Standards Commission on 1-31-2001 and filed 2-2-2001; operative 3-4-2001. Submitted to OAL for printing only (Register 2001, No. 13).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.