Section 3069 - Tanks
Universal Citation: 8 CA Code of Regs 3069
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) General Requirements.
(1) All tanks shall be of sufficient capacity to provide for an adequate liquid reserve to prevent the entrance of air or other gas into the system.
(2) The permissible minimum liquid level shall be clearly indicated.
(b) Storage and Discharge Tanks. Storage and discharge tanks shall conform to the following:
(1) They shall be covered and suitably vented to the atmosphere.
(2) They shall be so designed and constructed that, when completely filled, the factor of safety shall be at least 4 based on the ultimate strength of the material.
(3) Welding of parts on which safe operation depends shall conform to Section 3033(g).
1. New NOTE filed 12-8-86; effective thirtieth day thereafter (Register 86. No. 50).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.