Section 3093.4 - Protection of Hoistway Openings
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Hoistway doors conforming with Section 3020 shall be provided to protect each landing opening.
(b) Hoistway doors shall be provided with approved interlocks complying with Section 3021.
EXCEPTION to 3093.4(b): Interlocks may be zoned complying with subsection 3021(d)(1)(D).
(c) Hoistway doors shall be power-operated for special access elevators installed after Sept. 28, 2001.
NOTE: A low energy power-operated door is a door with power mechanisms that open and close the door upon receipt of an actuating signal and does not generate more kinetic energy than specified in ANSI/BHMA A156.19-1990.
(Title 24, Part 7, Section 7-3093.4)