California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 6 - Elevator Safety Orders
Group II - Elevator Installations for Which the Installation Contract Was Signed Before October 25, 1998
Article 15 - Special Access Elevators and Special Access Lifts
Section 3093.36 - Operation of the Stopping Devices
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) The final terminal stopping device shall act to prevent movement of the car in both directions of travel. The normal and final terminal stopping devices shall not control the same switches on the controller unless two or more separate and independent switches are provided, two of which shall be closed to complete the motor and brake circuit in each direction of travel.
(b) The switches required in subsection 3093.36(a) shall be positively opened mechanically as required by 3039(a).
(Title 24, Part 7, Section 7-3093.36)
1. New section filed 7-22-86; effective thirtieth day thereafter (Register 86, No. 36).
2. Amendment of section heading filed 8-29-2001; operative 9-28-2001 (Register 2001, No. 35).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.