(a) The final terminal stopping device shall act to prevent movement of the car in both directions of travel. The normal and final terminal stopping devices shall not control the same switches on the controller unless two or more separate and independent switches are provided, two of which shall be closed to complete the motor and brake circuit in each direction of travel.

(b) The switches required in subsection 3093.36(a) shall be positively opened mechanically as required by 3039(a).

(Title 24, Part 7, Section 7-3093.36)

1. New section filed 7-22-86; effective thirtieth day thereafter (Register 86, No. 36).
2. Amendment of section heading filed 8-29-2001; operative 9-28-2001 (Register 2001, No. 35).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.