California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 6 - Grounding
Section 2742.1 - Grounding of Supports, Enclosures and Equipment
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) The following shall be permanently and effectively grounded before the associated high-voltage equipment is energized.
EXCEPTION FOR SECTION 2742.1(a)(1):
Metal enclosures such as sleeves that are used to protect cable assemblies from physical damage need not be grounded.
(b) Exposed noncurrent-carrying metal parts of fixed equipment that may become energized shall be grounded under any of the following conditions:
EXCEPTIONS FOR SECTION 2742.1(b):
Exposed noncurrent-carrying metal parts of the following types of fixed equipment need not be grounded:
NOTE: Clearances prescribed by the California Public Utilities Commission shall apply where applicable if more protective.
(c) Effective grounding of all equipment shall be assured by the use of an equipment grounding conductor, where feasible, such that the path to ground will:
(d) Where high-voltage equipment and associated metal enclosures or structures are intentionally isolated from ground, provision shall be made to prevent any person who can make contact with ground from contacting the isolated equipment and associated metal enclosures or structures when such equipment is energized. Intentional grounds shall be applied after such equipment is de-energized and before access is permitted, in accordance with Work Procedures, Article 36.
1. New section filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.