Section 2739.1 - Grounding of Systems and Circuits-General
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Grounding of high-voltage systems and circuits is permitted, but is not mandatory unless specifically required elsewhere in these regulations. Where high-voltage systems are grounded, the applicable requirements of this Article 6 shall apply.
(b) Grounding connections shall be arranged to prevent objectionable current in the equipment grounding conductor during normal system operation. The temporary current carried by the equipment grounding conductor during fault conditions, while the grounding system is performing its intended protective function, is not objectionable.
(c) Grounding connections shall be clamp type, pressure type, welded, or other approved type.
(d) Grounding electrodes shall be of corrosion-resistant material and of adequate size, number, and location to effectively ground the system.
(e) Local piping systems, well casings, and the like shall not be used as system grounding electrodes unless their resistance to ground will be maintained low enough to insure effective grounding.
(f) Identification of conductors.
(g) Polarity of connections. No grounded conductor may be attached to any terminal or lead so as to reverse designated polarity.
1. Renumbering of former section 2739 to new section 2739.1, including amendment of section and NOTE, filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.