California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 39 - Signs and Outline Lighting-Exceeding 600 Volts
Section 2972 - Electric-Discharge Tubing

Universal Citation: 8 CA Code of Regs 2972

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Electric-discharge tubing shall conform to the following:

(a) Support. Tubing shall be adequately supported on noncombustible, nonabsorptive supports.

(Title 24, Part 3, Section 600-33(b).)

(b) Contact with Flammable Material and Other Surfaces. The tubing shall be free from contact with flammable material and shall be located where not normally exposed to physical damage. Where operating in excess of 7.5 kilovolts, the tubing shall be supported on noncombustible, nonabsorptive, insulating supports which maintain a spacing of not less than 1/4 inch between the tubing and the nearest surface.

(Title 24, Part 3, Section 600-33(c).)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.