Section 2940.18 - Current Transformer Secondaries

Universal Citation: 8 CA Code of Regs 2940.18

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) The employer shall ensure that employees do not open the secondary of a current transformer while the transformer is energized. If the employer cannot deenergize the primary of the current transformer before employees perform work on an instrument, a relay, or other section of a current transformer secondary circuit, the employer shall bridge the circuit so that the current transformer secondary does not experience an open-circuit condition.

1. New section filed 2-27-2018; operative 4-1-2018 (Register 2018, No. 9).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.