Section 2917 - Bonding and Equipment Grounding Conductor
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) All non-energized metal parts of electrical equipment and all metal raceways or cable sheaths shall be effectively grounded and bonded to all metal pipes and rails at the portal and at intervals not exceeding 1,000 feet throughout the tunnel.
(b) An equipment grounding conductor shall be run with circuit conductors inside the metal raceway or inside the multi-conductor cable jacket. The equipment grounding conductor shall be permitted to be insulated or bare.