Section 2917 - Bonding and Equipment Grounding Conductor

Universal Citation: 8 CA Code of Regs 2917

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) All non-energized metal parts of electrical equipment and all metal raceways or cable sheaths shall be effectively grounded and bonded to all metal pipes and rails at the portal and at intervals not exceeding 1,000 feet throughout the tunnel.

(b) An equipment grounding conductor shall be run with circuit conductors inside the metal raceway or inside the multi-conductor cable jacket. The equipment grounding conductor shall be permitted to be insulated or bare.

1. Editorial correction adding NOTE filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.