Section 2712 - Atmospheric and Environmental Protection
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Electrical installations and equipment shall be constructed or protected to withstand the atmospheric and environmental conditions to which they will be subjected.
(b) Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures.
(c) Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures.
EXCEPTION FO R (c)(1): Nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface.
(d) Switches, circuit breakers, and switchboards.
Switches, circuit breakers, and switchboards installed in wet locations shall be enclosed in weatherproof enclosures.