Section 2884 - Generator Circuit Protection
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Generator Grounding. Generator windings, if grounded, and frames shall be grounded in accordance with Article 6.
(b) General. The high-voltage circuit of each generator shall include coordinated protection capable of detecting and automatically interrupting overload and fault currents in the generator, the generator circuit conductors, and the generator control.
EXCEPTION: The overload protection for generators in supervised locations need not automatically trip the switching device, provided it initiates an alarm for the operator to take appropriate action.
(c) Fault Current Protection.
(d) Overload Protection.
(e) Combination Protection. Combination fault interruption and overload protection shall be permitted to be provided by the same device.
(Title 24, Part 3, Section 3-445 - 10.)