Article 26 - Metal-Enclosed Power Switchgear and Industrial Control Assemblies
Section 2871 - Interlocks-Circuit Breakers

Universal Citation: 8 CA Code of Regs 2871

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Circuit breakers equipped with stored energy mechanisms shall be designed to prevent the release of the stored energy unless the mechanism has been fully charged.

(b) Mechanical interlocks shall be provided in the housing to prevent the complete withdrawal of the circuit breaker from the housing when the stored energy mechanism is in the fully charged position. In lieu of the above interlock, a suitable device may be provided which prevents the complete withdrawal of the circuit breaker until the closing function is blocked.

(Title 24, Part 3, Section 710-24(p).)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.