Section 2869 - Location of Devices

Universal Citation: 8 CA Code of Regs 2869
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Control and instrument transfer switch handles or push buttons shall be located in a readily accessible location at an elevation not in excess of 78 inches.

EXCEPTION: NO. 1: Operating handles requiring more than 50 pounds of force shall not be higher than 66 inches in either the open or closed position.

EXCEPTION: NO. 2: Operating handles for infrequently operated devices, such as drawout fuses, fused potential or control transformers and their primary disconnects, and bus transfer switches, need not be readily accessible, provided they are otherwise safely operable and serviceable from a portable platform.

(Title 24, Part 3, Section 710-24 (l).)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.