Section 2860 - Guarding of High-Voltage Energized Parts Within a Compartment

Universal Citation: 8 CA Code of Regs 2860
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

When access for other than visual inspection is required to a compartment which contains energized high-voltage parts, barriers shall be provided (a) to prevent accidental contact with energized parts, and (b) to prevent tools or other equipment from being dropped on energized parts.

(Title 24, Part 3, Section 710-24(c).)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.