California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 20 - Interrupting and Isolating Devices
Section 2841 - Isolation

Universal Citation: 8 CA Code of Regs 2841

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Means shall be provided to isolate each circuit breaker or circuit breaker installation from all sources of potential.

(b) The isolating means shall provide a visible gap in the electrical circuit adequate for the operating voltage.

(c) Isolating or disconnecting switches (with no interrupting rating) shall be mechanically interlocked with the circuit breaker or shall be provided with prominently displayed caution signs in accordance with Section 2835 to prevent switching load current.

(d) The isolating means shall be permitted to be individually or group operated.

(Title 24, Part 3, Section 3-710 - 21(a)(11).)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Editorial correction of subsection (c) filed 11-3-83 (Register 83, No. 45).
3. Amendment of subsection (d) filed 12-10-87; operative 1-9-88 (Register 88, No. 1).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.