California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 20 - Interrupting and Isolating Devices
Section 2834 - Fused Interrupter Switches

Universal Citation: 8 CA Code of Regs 2834

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Fused interrupter switches shall be so installed that all supply terminals shall be at the top of the switch enclosure.

EXCEPTION: Supply terminals are not required to be at the top of the switch enclosure if barriers are installed to prevent persons from accidentally contacting energized parts or dropping tools or fuses into energized arts.

(b) Where fuses can be energized by backfeed, a sign shall be placed on the enclosure door reading, "WARNING--FUSES MAY BE ENERGIZED BY BACKFEED."

(Title 24, Part 3, Section 710-24(o).)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Editorial correction of subsection (c) filed 11-3-83 (Register 83, No. 45).
3. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.