Section 2834 - Fused Interrupter Switches
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Fused interrupter switches shall be so installed that all supply terminals shall be at the top of the switch enclosure.
EXCEPTION: Supply terminals are not required to be at the top of the switch enclosure if barriers are installed to prevent persons from accidentally contacting energized parts or dropping tools or fuses into energized arts.
(b) Where fuses can be energized by backfeed, a sign shall be placed on the enclosure door reading, "WARNING--FUSES MAY BE ENERGIZED BY BACKFEED."
(Title 24, Part 3, Section 710-24(o).)