California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 20 - Interrupting and Isolating Devices
Section 2833 - Interrupter Switches
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Rating.
(b) Enclosure. Circuit breaker installations located indoors shall consist of metal-enclosed units or fire-resistant cell-mounted units, or shall be installed in a room of at least 2-hour fire-resistive construction, or in a transformer vault.
(c) Installation Requirements. Interrupter switches shall be so installed that the center of the grip of the operating handle of the switch, when in its uppermost position, will be not more than 6 1/2 feet above the floor or working platform.
(d) Enclosures as Raceways. Switch enclosures shall not be used as raceways for conductors feeding through, or tapping off, to other switches, unless adequate space is provided for this purpose.
(e) Switching of Conductors. The switching mechanism shall be arranged to be operated from a location where the operator is not exposed to energized parts and shall be arranged to open all ungrounded conductors of the circuit simultaneously with one operation. Switches shall be arranged to be locked in the open position. Metal-enclosed switches shall be operable from outside the enclosure.
(f) Fuses. Fuses installed with interrupter switches shall comply with the requirements of Article 24.
(g) Readily and Safely Accessible. Interrupter switches, except those installed on poles or structures, shall be so located that they may be operated or maintained from a readily and safely accessible place.
(h) Identification. Interrupter switches shall have a permanent and legible nameplate including the following information: manufacturer's type or designation, continuous current rating, interrupting current rating, momentary current rating, fault closing rating, and maximum voltage rating.
(i) Stored Energy for Opening. The stored energy operator shall be permitted to be left in the uncharged position after the switch has been closed if a single movement of the operating handle charges the operator and opens the switch.
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Editorial correction of subsection (c) filed 11-3-83 (Register 83, No. 45).
3. Amendment filed 12-10-87; operative 1-9-88 (Register 88, No. 1).
4. Amendment of subsection (b), new subsections (b)(1)-(2), repealer of subsection (f), subsection relettering and amendment of NOTE filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.