California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 19 - Outdoor Wiring
Section 2824 - Overhead Lines
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Supports. Open conductors shall be supported on insulators of sufficient mechanical and dielectric strength for the application.
(Title 24, Part 3, Section 3-710 - 84(a).)
(b) Vertical Clearances. All conductors of outside wiring shall comply with clearances specified in Rule 37, General Order No. 95, 1981 Edition, Rules for Overhead Electric Line Construction of the California Public Utilities Commission, which is hereby incorporated by reference. The following table for overhead conductors and sign clearances is extracted from Tables 1 and 2A of these rules:
Minimum Clearance |
||||
Overhead Conductors Nature of Vertical Clearance |
750- 20,000 volts |
Over 20,000 volts |
||
1. | Above tracks of railroads which transport freight cars where not operated by overhead contact wires.......................... | 28 feet | 34 feet | |
2. | Above tracks of railroads operated by overhead contact wires.......................... | 30 feet | 34 feet | |
3. | Above and along thoroughfares in urban areas and above thoroughfares in rural areas.......................... | 25 feet | 30 feet | |
4. | Above areas (other than thoroughfares) where it is possible to drive vehicles.......................... | 25 feet | 30 feet | |
5. | Above areas accessible to pedestrians only.......................... | 17 feet | 25 feet | |
6. | Above structures.......................... | 12 feet | 12 feet | |
7. | Vertical clearance above all signs upon which men can walk.......................... | 12 feet | 12 feet | |
8. | Vertical clearance above all signs upon which men cannot walk.......................... | 8 feet | 8 feet | |
9. | Vertical clearance under signs.......................... | Prohibited | Prohibited | |
10. | Horizontal clearance from signs.......................... | 6 feet | 6 feet |
(Title 24, Part 3, Section 3-710 - 85(a).)
(c) Clearance from Buildings. Open high-voltage conductors shall be substantially supported independently of buildings or structures and shall have a clearance from buildings or structures as follows:
(Title 24, Part 3, Section 3-710 - 85(b).)
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment of subsections (b) and (c) filed 12-10-87; operative 1-9-88 (Register 88, No. 1).
3. Editorial correction of subsection (b) (Register 2019, No. 10).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.