California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 2 - High-Voltage Electrical Safety Orders
Article 18 - Conductors
Section 2816 - Insulation
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Conductors shall be insulated, except where uninsulated conductors are specifically permitted by these orders, and shall have a voltage rating not less than the operating voltage of the circuit.
(b) The conductor insulation shall be of a type that is approved for the voltage, operating temperature, and location of use.
(c) Distinguishable. Insulated conductors shall be distinguishable by appropriate color or other suitable means as being grounded conductors, ungrounded conductors, or equipment grounding conductors.
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 12-10-87; operative 1-9-88 (Register 88, N. 1).
3. Amendment of section and NOTE filed 4-1-2009; operative 4-1-2009. Submitted to OAL for printing only pursuant to Labor Code section 142.3 (Register 2009, No. 14).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.