Section 2773 - Low-Voltage Wiring
Universal Citation: 8 CA Code of Regs 2773
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
Secondary control devices and wiring which are provided as part of the metal-enclosed bus run shall be isolated by grounded metal barriers from all primary circuit elements with the exception of short lengths of wire, such as at instrument transformer terminals.
(Title 24, Part 3, Section 364-30.)
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.