Section 2375.7 - Conductors on Poles

Universal Citation: 8 CA Code of Regs 2375.7

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Conductors on poles shall have a separation of not less than 1 foot (305 mm) where not placed on racks or brackets. Conductors supported on poles shall provide a horizontal climbing space not less than the following:

(a) Power conductors below communication conductors--30 in. (762 mm);

(b) Power conductors alone or above communication conductors:

(1) 300 volts or less--24 in. (610 mm),

(2) Over 300 volts--30 in. (762 mm);

(c) Communication conductors below power conductors--same as power conductors; and

(d) Communications conductors alone--no requirement.

1. New section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19). For prior history, see Register 79, No. 32.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.