Section 2375.19 - Clearances from Buildings
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Over roofs. Open wiring and cables shall have a clearance of not less than 8 feet from the highest point of roofs over which they pass.
EXCEPTION: No. 1: Where the voltage between conductors does not exceed 300 and the roof has a slope of not less than 4 inches in 12 inches, a reduction in clearance to 3 feet shall be permitted.
EXCEPTION: No. 2: Where the voltage between conductors does not exceed 300, a reduction in clearance over the overhanging portion of the roof to 18 inches shall be permitted if:
EXCEPTION: No. 3: The area above a roof surface subject to pedestrian or vehicular traffic shall have a vertical clearance from the roof surface in accordance with the clearance requirements of Section 2375.18.
(b) Horizontal Clearances. Open wiring and cables not attached to a building shall have a minimum horizontal clearance of 3 feet.
(c) Final Spans.
1. Repealer and new section filed 8-9-79; effective thirtieth day thereafter (Register 79, No. 32).
2. Editorial correction filed 11-2-83 (Register 83, No. 45).
3. Amendment filed 8-27-86; effective thirtieth day thereafter (Register 86, No. 37).
4. Amendment filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.