PERMANENTLY INSTALLED POOLS
Section 2569.20 - Underwater Equipment
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) A ground-fault circuit interrupter shall be installed in the branch circuit supplying underwater fixtures operating at more than 15 volts. Equipment installed underwater shall be identified for the purpose.
(b) No underwater lighting fixtures may be installed for operation at over 150 volts between conductors.
(c) A lighting fixture facing upward shall have the lens adequately guarded to prevent contact by any person.