California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 1 - Low-Voltage Electrical Safety Orders
Article 74 - Cranes and Hoists
Section 2561.32 - Disconnecting Means for Cranes and Monorail Hoists
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) A motor-circuit switch, molded case switch, or circuit breaker shall be provided in the leads from the runway contact conductors or other power supply on all cranes and monorail hoists.
EXCEPTION: The disconnecting means may be omitted where a monorail hoist or hand-propelled crane bridge installation meets all of the following conditions:
(b) The disconnecting means shall be capable of being locked in the open position.
(c) Means shall be provided at the operating station to open the power circuit to all motors of the crane or monorail hoist where the disconnecting means is not readily accessible from the crane or monorail hoist operating station.
1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment deleting subsection (a) designation only filed 8-27-86; effective thirtieth day thereafter (Register 86, No. 37).
3. Editorial correction of printing error in EXCEPTION 3 (Register 94, No. 26).
4. Amendment of section and NOTE filed 8-25-2003; operative 9-24-2003 (Register 2003, No. 35).
5. Amendment of section heading and repealer and new section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.