Section 2561.11 - Wiring Method

Universal Citation: 8 CA Code of Regs 2561.11
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Conductors shall be enclosed in a raceway or shall be Type MC or MI cable.

EXCEPTION: No. 1: Contact conductors so located or arranged that persons cannot inadvertently touch energized parts or bring conducting material into contact with them.

EXCEPTION: No. 2: Short lengths of open conductors at resistors, collectors, DC motors and other equipment so located or arranged that persons cannot inadvertently touch energized parts or bring conducting material into contact with them.

EXCEPTION: No. 3: Where flexibility is necessary, multi-conductor cable may be used.

EXCEPTION: No. 4: Where multi-conductor cable is used with a suspended push button station, the station shall be supported in some suitable manner that protects the electrical connections against strain.

(Title 24, Part 3, Section 610-11.)

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment filed 8-27-86; effective thirtieth day thereafter (Register 86, No. 37).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.