Article 74 - Cranes and Hoists
Section 2561.11 - Wiring Method
Conductors shall be enclosed in a raceway or shall be Type MC or MI cable.
EXCEPTION: No. 1: Contact conductors so located or arranged that persons cannot inadvertently touch energized parts or bring conducting material into contact with them.
EXCEPTION: No. 2: Short lengths of open conductors at resistors, collectors, DC motors and other equipment so located or arranged that persons cannot inadvertently touch energized parts or bring conducting material into contact with them.
EXCEPTION: No. 3: Where flexibility is necessary, multi-conductor cable may be used.
EXCEPTION: No. 4: Where multi-conductor cable is used with a suspended push button station, the station shall be supported in some suitable manner that protects the electrical connections against strain.
(Title 24, Part 3, Section 610-11.)