Section 2560.10 - Clearances
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Vertical and Horizontal. Signs and outline system enclosures shall have not less than the vertical and horizontal clearances from open conductors specified in the following table:
TABLE 2560.10
CLEARANCES
Vertical clearance above all signs upon which persons can walk.......................... | 8 feet |
Vertical clearance above all signs upon which persons cannot walk.......................... | 3 feet |
Vertical clearance under signs.......................... | 3 feet |
Horizontal clearance from signs.......................... | 3 feet |
(Title 24, Part 3, Section 3-600 - 10(a).)
(b) Elevation. The bottom of sign and outline lighting enclosures shall not be less than 16 feet above areas accessible to vehicles.
EXCEPTION: The bottom of such enclosures may be less than 16 feet above areas accessible to vehicles where such enclosures are protected from physical damage.
(Title 24, Part 3, Section 600-10(b).)