California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 1 - Low-Voltage Electrical Safety Orders
Article 59 - Hazardous (Classified) Locations
Section 2540.11 - Class I, Zone 0, 1, and 2 Locations
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Scope. Employers may use the zone classification system as an alternative to the division classification system for electric and electronic equipment and wiring for all voltages in Class I, Zone 0, Zone 1, and Zone 2 hazardous (classified) locations where fire or explosion hazards may exist due to flammable gases, vapors, or liquids.
(b) Location and General Requirements.
(c) Threading. All threaded conduit shall be threaded with an NPT [National (American) Standard Pipe Taper] standard conduit cutting die that provides 3/4 -in. taper per foot. The conduit shall be made wrench tight to prevent sparking when fault current flows through the conduit system and to ensure the explosion-proof or flame-proof integrity of the conduit system where applicable.
Equipment provided with threaded entries for field wiring connection shall be installed in accordance with subsection (1) or (2) as follows:
(d) Protection Techniques. One or more of the following protection techniques shall be used for electric and electronic equipment in hazardous (classified) locations classified under the zone classification system.
(e) Special Precaution. This Article (Article 59) requires equipment construction and installation that will ensure safe performance under conditions of proper use and maintenance.
NOTE to subsection (e): Low ambient conditions require special consideration. Electric equipment depending on the protection techniques described by subsection (d)(1) of this section may not be suitable for use at temperatures lower than -20 degrees C (-4 degrees F) unless they are approved for use at lower temperatures. However, at low ambient temperatures, flammable concentrations of vapors may not exist in a location classified Class I, Zone 0, 1, or 2 at normal ambient temperature.
(f) Listing and Marking.
NOTE to subsection (f)(2)(B): An example of such a required marking is "Class I, Zone 0, AEx ia IIC T6." See Figure S-1 for an explanation of this marking.
EXCEPTION: to (f)(2): Equipment that the employer demonstrates will provide protection from the hazards arising from the flammability of the gas or vapor and the zone of location involved and will be recognized as providing such protection by employees need not be marked.
NOTE for EXCEPTION: The National Electrical Code, NFPA 70, contains guidelines for determining the type and design of equipment and installations that will meet this provision.
Figure S-1--Example Marking for Class I, Zone 0, AEx ia IIC T6
1. New section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.