Section 2534.8 - Disconnecting Means
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
A disconnecting means shall be provided in each ungrounded conductor for each capacitor bank and shall meet the following requirements:
(a) The disconnecting means shall open all ungrounded conductors simultaneously.
(b) The disconnecting means shall be permitted to disconnect the capacitor from the line as a regular operating procedure.
(c) The rating of the disconnecting means shall not be less than 135 percent of the rated current of the capacitor.
EXCEPTION: A separate disconnecting means shall not be required where a capacitor is connected on the load side of a motor controller.