Section 2534.6 - Drainage of Stored Charge
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
Capacitors shall be provided with an automatic means of draining the stored charge after the capacitor is disconnected from its source of supply.
(a) Time of Discharge. The residual voltage of a capacitor shall be reduced to 50 volts or less within one minute after the capacitor is disconnected from the source of supply.
(b) Means of Discharge. The discharge circuit shall be either permanently connected to the terminals of the capacitor or capacitor bank, or provided with automatic means of connecting it to the terminals of the capacitor bank on removal of voltage from the line. Manual means of switching or connecting the discharge circuit shall not be used.