Article 58 - Capacitors
Section 2534.6 - Drainage of Stored Charge

Universal Citation: 8 CA Code of Regs 2534.6

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Capacitors shall be provided with an automatic means of draining the stored charge after the capacitor is disconnected from its source of supply.

(a) Time of Discharge. The residual voltage of a capacitor shall be reduced to 50 volts or less within one minute after the capacitor is disconnected from the source of supply.

(b) Means of Discharge. The discharge circuit shall be either permanently connected to the terminals of the capacitor or capacitor bank, or provided with automatic means of connecting it to the terminals of the capacitor bank on removal of voltage from the line. Manual means of switching or connecting the discharge circuit shall not be used.

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment of section and NOTE filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.