CONTROL AND PROTECTION OF APPLIANCES
Section 2522.23 - Disconnection of Stationary Appliances
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) For stationary appliances rated at not over 300 volt amperes or 1/8 horsepower, the branch circuit overcurrent device shall be permitted to serve as the disconnecting means.
(Title 24, Part 3, Section 422-21(a).)
(b) For stationary appliances of greater rating, the branch circuit switch or circuit breaker shall be permitted to serve as the disconnecting means where readily accessible to the user of the appliance.
(Title 24, Part 3, Section 422-21(b).)
(c) For cord-connected appliances, such as free-standing household-type ranges and clothes dryers, a separable connector or an attachment plug and receptacle shall be permitted to serve as the disconnecting means. Attachment plugs and connectors shall comply with Section 2522.22(c).
For household electric ranges, an attachment plug and receptacle connection at the rear base of a range, if it is accessible from the front by removal of a drawer, shall be considered as meeting the intent of this rule.
(Title 24, Part 3, Section 422-22(a) and (b).)