Section 2500.23 - Conductor Identification
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) A conductor of a flexible cord or cable that is used as a grounded conductor or an equipment grounding conductor shall have a continuous identifying marker readily distinguishing it from the other conductor or conductors.
(b) Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, and STOO flexible cords and Types G, G-GC, PPE, and W flexible cables shall be durably marked on the surface at intervals not exceeding 24 in. (610 mm) with the type designation, size, and number of conductors.