Section 2473.1 - Conductors Entering Boxes, Cabinets, or Fittings
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.
(b) Unused openings in cabinets, boxes, and fittings shall be effectively closed.
(c) Where cable is used, each cable shall be secured to the cabinet, cutout box, or meter socket enclosure. However, where cable with an entirely nonmetallic sheath enters the top of a surface-mounted enclosure through one or more nonflexible raceways not less than 18 in. (457 mm) or more than 10 feet (3.05 m) in length, the cable need not be secured to the cabinet, box, or enclosure provided all of the following conditions are met: